SB1000 RS485 communication is not working
Check the installation
- Confirm that A and B are connected consistently across the RS485 bus.
- Confirm that baud rate, parity, stop bits, and Modbus address match the connected equipment.
- Disconnect other devices temporarily to rule out a bus wiring, addressing, or termination problem.
Run the built-in RS485 self-test
The self-test runs inside the affected SB1000 and cannot be started from the public WordPress site.
- Open the affected SB1000 web interface and go to Help → Serial Broker – Troubleshooting.
- Disconnect both RS485 ports from the field bus.
- Connect Port 1 A to Port 2 A.
- Connect Port 1 B to Port 2 B.
- Start the RS485 self-test shown in the device Help page and follow its result.
If the device web interface is unavailable, resolve the power or network connection first. If the self-test fails with only the loopback wiring connected, record the result and contact Varibits support.