Description
TCP to RS485 gateway – Modbus TCP / RTU
The Serial Broker 1000 (SB1000) is a compact and flexible gateway for seamless conversion from Modbus RTU to Modbus TCP, BACnet and MQTT. The unit mounts on a DIN rail and is ideal for building automation, industry and technical installations where you want to integrate existing Modbus RTU-based devices into an Ethernet-based network. A highly intuitive user interface makes setup easier than on other products.
Flexible applications
Modbus TCP to RTU gateway
Connect Ethernet-based systems to RS485 devices.
Modbus RTU to TCP gateway
Make existing RTU installations available over IP.
RTU to RTU
Signal splitter: share slaves between a Modbus RTU master and a Modbus TCP master
Signal booster / repeater
Baud rate converter
Virtual COM port over TCP/IP
This makes the SB1000 a very flexible tool when modernising older plants or integrating different systems.
On the Ethernet side we support Modbus TCP, BACnet and MQTT.
Technical details
-
2 × RS485 ports
-
RJ45 Ethernet (10/100 Mbit)
-
2.4 GHz WiFi (configurable as AP or client)
-
1 digital input
-
9–24 V AC/DC supply (polarity independent)
-
Built-in temperature sensor
-
Software-controlled BIAS and end-of-line termination on RS485
-
Web-based configuration
-
Firmware updates via web
- Width is only 3 standard DIN modules, 53.4 mm
Datasheet
Live demo
PS: The live demo is a device running at our lab. It is liimited to 2 simultaneous connections.
If the connection currently is in use, please try again at a later time.
When modifying settings, such as name, location ,etc, this will be visible to other guests.
The device resets its settings after 10 minutes of inactivity.
There is a Belimo 22DTM-16 connected to RS485-1, device ID #9.
Supported Modbus RTU Devices
Search the current SB1000 device library by model, manufacturer, or equipment type.
Filter by category
Filter by manufacturer
ABB ACH580
ABB ACH580 / ACQ580 / ACS580 HVAC drives via Modbus RTU/TCP (default ABB Drives profile, 16-bit access)
- Library ID
abb_ach580- Access
- 30 read, 10 write
- Register areas
- holding
Badger Meter ModMAG M2000 (Advanced)
Badger Meter ModMAG M2000 electromagnetic flow meter via Modbus RTU daughterboard (RS232/RS485). Baud 9600/19200/38400, default 8E1. Float32 IEEE-754 big-endian (ABCD).
- Library ID
badger_m2000_advanced- Access
- 69 read, 62 write
- Register areas
- holding
Badger Meter ModMAG M2000 (Basic)
Badger Meter ModMAG M2000 electromagnetic flow meter via Modbus RTU daughterboard (RS232/RS485). Baud 9600/19200/38400, default 8E1. Float32 IEEE-754 big-endian (ABCD).
- Library ID
badger_m2000_basic- Access
- 6 read
- Register areas
- holding
Belimo 22ADP (Advanced)
Belimo 22ADP diff. press./vol. flow sensor. Single/dual. SI used. DIP S1, pos 6 is OFF. Reg 405 is set to 0.
- Library ID
belimo_22adp_advanced- Access
- 36 read, 22 write
- Register areas
- holding
Belimo 22ADP (Basic)
Belimo 22ADP diff. press./vol. flow sensor. Single/dual. SI used. DIP S1, pos 6 is OFF. Reg 405 is set to 0.
- Library ID
belimo_22adp_basic- Access
- 6 read, 2 write
- Register areas
- holding
Belimo 22DTH (Advanced)
Belimo 22DTH room/duct sens for temp and rel humid. SI-units used.
- Library ID
belimo_22dth_advanced- Access
- 34 read, 22 write
- Register areas
- holding
Belimo 22DTH (Basic)
Belimo 22DTH room/duct sens for temp and rel humid. SI-units used.
- Library ID
belimo_22dth_basic- Access
- 5 read
- Register areas
- holding
Belimo 22DTM (Advanced)
Belimo 22DTM room sensor for temperature, relative humidity and CO2 (Modbus RTU)
- Library ID
belimo_22dtm_advanced- Access
- 39 read, 26 write
- Register areas
- holding
Belimo 22DTM (Basic)
Belimo 22DTM room sensor for temperature, relative humidity and CO2 (Modbus RTU)
- Library ID
belimo_22dtm_basic- Access
- 5 read
- Register areas
- holding
Belimo 22UTH (Advanced)
Belimo 22UTH duct sensor for temperature and relative humidity (Modbus RTU)
- Library ID
belimo_22uth_advanced- Access
- 34 read, 22 write
- Register areas
- holding
Belimo 22UTH (Basic)
Belimo 22UTH duct sensor for temperature and relative humidity (Modbus RTU)
- Library ID
belimo_22uth_basic- Access
- 4 read
- Register areas
- holding
Belimo Energy Valve V3 (Advanced)
Belimo Energy Valve V1/V2/V3 Modbus RTU/TCP - electronic pressure-independent characterised control valve with energy monitoring
- Library ID
belimo_energy_valve_v3_advanced- Access
- 56 read, 18 write
- Register areas
- holding
Belimo Energy Valve V3 (Basic)
Belimo Energy Valve V1/V2/V3 Modbus RTU/TCP - electronic pressure-independent characterised control valve with energy monitoring
- Library ID
belimo_energy_valve_v3_basic- Access
- 31 read, 12 write
- Register areas
- holding
Belimo Energy Valve V4.2 (Advanced)
Belimo Energy Valve V4 (DN 15...50) Modbus RTU/TCP - electronic pressure-independent characterised control valve with energy monitoring
- Library ID
belimo_energy_valve_v4_2_advanced- Access
- 114 read, 36 write
- Register areas
- holding
Belimo Energy Valve V4.2 (Basic)
Belimo Energy Valve V4 (DN 15...50) Modbus RTU/TCP - electronic pressure-independent characterised control valve with energy monitoring
- Library ID
belimo_energy_valve_v4_2_basic- Access
- 57 read, 15 write
- Register areas
- holding
Belimo LMV-D3-MOD
VAV
- Library ID
belimo-lmv-d3-mod- Access
- Not available
- Register areas
- 3
Trox BM0
Trox BM0 Modbus RTU / BACnet MS/TP bus interface for TVR/TVJ/TVT/TVM fan-based VAV terminal units (Belimo D3-M/B TR actuators)
- Library ID
trox_bm0- Access
- 29 read, 12 write
- Register areas
- holding
Bell & Gossett Danfoss VLT Modbus RTU
Bell & Gossett / Danfoss VLT frequency converter (HVAC FC102 / AQUA FC202 / Automation FC302) generic Modbus RTU FC profile
- Library ID
bg_danfoss_vlt_modbus- Access
- 41 read, 21 write
- Register areas
- coil, holding
Bender ISOMETER iso685
Insulation monitoring device for unearthed IT AC/DC systems. Covers iso685(W)-D/-S, iso685-D-B, iso685-D-P (EDS locating), isoRW685W-D and isoHR685-D-I-B variants per the iso685 device family Modbus settings appendix.
- Library ID
bender_iso685- Access
- 339 read, 107 write
- Register areas
- holding
Carel uC2SE
Process chiller controller
- Library ID
carel_uc2se- Access
- 168 read, 134 write
- Register areas
- coil, holding
Carel uChiller
Air/water and water/water chiller and heat Pmp controller
- Library ID
carel_uchiller- Access
- 419 read, 269 write
- Register areas
- coil, discrete, holding, input
Carel uChiller 3
Process chiller/heat pump controller (C3 platform)
- Library ID
carel_uchiller3- Access
- 245 read, 141 write
- Register areas
- coil, holding
Carlo Gavazzi EM111
Energy meter
- Library ID
EM111- Access
- 19 read
- Register areas
- input
Carlo Gavazzi EM112
Energy meter
- Library ID
EM112- Access
- 19 read
- Register areas
- input
Carlo Gavazzi EM21
Energy meter
- Library ID
EM21- Access
- 31 read
- Register areas
- input
Carlo Gavazzi EM210
Energy meter
- Library ID
EM210- Access
- 44 read
- Register areas
- input
Carlo Gavazzi EM24
Energy meter
- Library ID
EM24- Access
- 36 read
- Register areas
- input
Carlo Gavazzi EM271 (Advanced)
Energy meter
- Library ID
EM271_advanced- Access
- 57 read
- Register areas
- input
Carlo Gavazzi EM271 (Basic)
Energy meter
- Library ID
EM271_basic- Access
- 15 read
- Register areas
- input
Carlo Gavazzi EM330
Energy meter
- Library ID
EM330- Access
- 34 read
- Register areas
- input
Carlo Gavazzi EM340
Energy meter
- Library ID
EM340- Access
- 38 read
- Register areas
- input
Carlo Gavazzi EM530 (Advanced)
Energy meter
- Library ID
EM530_advanced- Access
- 65 read
- Register areas
- input
Carlo Gavazzi EM530 (Basic)
Energy meter
- Library ID
EM530_basic- Access
- 17 read
- Register areas
- input
Carlo Gavazzi EM540 (Advanced)
Energy meter
- Library ID
EM540_advanced- Access
- 76 read
- Register areas
- input
Carlo Gavazzi EM540 (Basic)
Energy meter
- Library ID
EM540_basic- Access
- 17 read
- Register areas
- input
Carlo Gavazzi EM630 (Advanced)
Energy meter
- Library ID
EM630_advanced- Access
- 95 read
- Register areas
- input
Carlo Gavazzi EM630 (Basic)
Energy meter
- Library ID
EM630_basic- Access
- 17 read
- Register areas
- input
Carlo Gavazzi EM640 (Advanced)
Energy meter
- Library ID
EM640_advanced- Access
- 95 read
- Register areas
- input
Carlo Gavazzi EM640 (Basic)
Energy meter
- Library ID
EM640_basic- Access
- 17 read
- Register areas
- input
Carlo Gavazzi ET112
Energy meter
- Library ID
ET112- Access
- 12 read
- Register areas
- input
Carlo Gavazzi ET330
Energy meter
- Library ID
ET330- Access
- 41 read
- Register areas
- input
Carlo Gavazzi ET340
Energy meter
- Library ID
ET340- Access
- 40 read
- Register areas
- input
Carlo Gavazzi WM15 (Advanced)
Energy meter
- Library ID
WM15_advanced- Access
- 82 read
- Register areas
- input
Carlo Gavazzi WM15 (Basic)
Energy meter
- Library ID
WM15_basic- Access
- 17 read
- Register areas
- input
Circutor CBS-4 series
4-channel earth-leakage relay with RS-485 Modbus RTU (CBS-4C / CBS-4C-NC variants)
- Library ID
circutor_cbs4- Access
- 25 read, 17 write
- Register areas
- holding, input
Circutor CVM-MINI
Circutor CVM-MINI power analyzer (M98174001 manual)
- Library ID
circutor_cvm_mini- Access
- 45 read
- Register areas
- holding
Danfoss VLT Micro Drive FC 51
Frequency converter - Modbus RTU
- Library ID
danfoss_vlt_fc51- Access
- 217 read, 165 write
- Register areas
- holding
Eastron SDM630 Modbus (Advanced)
3-phase multifunction DIN-rail energy meter with Modbus RTU
- Library ID
eastron_sdm630_advanced- Access
- 96 read, 9 write
- Register areas
- holding, input
Eastron SDM630 Modbus (Basic)
3-phase multifunction DIN-rail energy meter with Modbus RTU
- Library ID
eastron_sdm630_basic- Access
- 17 read
- Register areas
- input
Eastron SMART X96-5A-MT (Advanced)
96x96 panel-mount multifunction energy analyzer with Modbus RTU
- Library ID
eastron_smart_x96_advanced- Access
- 59 read, 4 write
- Register areas
- holding, input
Eastron SMART X96-5A-MT (Basic)
96x96 panel-mount multifunction energy analyzer with Modbus RTU
- Library ID
eastron_smart_x96_basic- Access
- 17 read
- Register areas
- input
DSZ15DZMOD
3-phase energy meter v1.6
- Library ID
dsz15dzmod- Access
- 12 read, 2 write
- Register areas
- holding, input
Grundfos CIM 200 Modbus RTU (E-pump)
Grundfos CIM/CIU 200 Modbus RTU gateway attached to an E-pump (MAGNA3, TPE/TPE Series 2000, NBE/NKE, CUE, MGE models C-K)
- Library ID
grundfos_cim200_pump- Access
- 151 read, 35 write
- Register areas
- holding
Grundfos CIM 200 Modbus RTU (Hydro MPC booster)
Grundfos CIM/CIU 200 Modbus RTU gateway for Hydro MPC/GENIECON/Multi-B/Multi-E/TPED/MAGNA3-D booster systems.
- Library ID
grundfos_cim200_booster- Access
- 268 read, 68 write
- Register areas
- holding
Grundfos LC 2X1/LC 2X2 level control
Grundfos Level Control LC 2X1/LC 2X2 (LC 231/241/242) via CIM 200 Modbus RTU gateway. Two-pump wastewater/water supply controller.
- Library ID
grundfos_level_control- Access
- 189 read, 36 write
- Register areas
- holding
Grundfos MP 204 motor protector
Grundfos MP 204 motor protector via CIU 200 / CIM 200 Modbus RTU gateway.
- Library ID
grundfos_mp204- Access
- 110 read, 25 write
- Register areas
- holding
Grundfos Smart Digital Dosing (DDA/DDC/DDE)
Grundfos Smart Digital Dosing pumps (DDA/DDC/DDE incl. DDA-S, DDA XL, DDA-C) via built-in SoftCIM Modbus RTU or external CIM 200.
- Library ID
grundfos_smart_digital_dosing- Access
- 126 read, 41 write
- Register areas
- holding
Grundfos SoftCIM Modbus RTU (MGE)
Built-in SoftCIM Modbus RTU on MGE motors with Functional Module FM310/311/110 (RS485 A/Y/B). Register map matches CIM 200 except SlaveMinReplyDelay and software-defined address are unsupported.
- Library ID
grundfos_softcim_mge- Access
- 148 read, 32 write
- Register areas
- holding
Hugo Mueller GS 3x.40 mod
Room temperature and humidity sensor with Modbus RTU (GS 30.40 / GS 31.40)
- Library ID
hugo_mueller_gs_3x40- Access
- 38 read, 22 write
- Register areas
- coil, discrete, holding, input
Hugo Mueller GS 4x.40 mod
Room air-quality sensor with CO2, temperature, humidity and pressure (GS 40.40 / GS 41.40)
- Library ID
hugo_mueller_gs_4x40- Access
- 43 read, 25 write
- Register areas
- coil, discrete, holding, input
Hugo Mueller TS 3x.40 mod
Room temperature sensor with Modbus RTU (TS 30.40 / TS 31.40)
- Library ID
hugo_mueller_ts_3x40- Access
- 27 read, 19 write
- Register areas
- coil, discrete, holding, input
IME Conto D4-Pd
Three-phase static energy meter (Modbus RTU)
- Library ID
ime_conto_d4_pd- Access
- 42 read, 1 write
- Register areas
- holding
IME Nemo 96HD (Advanced)
3-phase network analyser 96x96 panel-mount (Modbus RTU)
- Library ID
ime_nemo_96hd_advanced- Access
- 115 read, 2 write
- Register areas
- holding
IME Nemo 96HD (Basic)
3-phase network analyser 96x96 panel-mount (Modbus RTU)
- Library ID
ime_nemo_96hd_basic- Access
- 17 read
- Register areas
- holding
IME Nemo D4-Le (Advanced)
Multifunction 3-phase network analyser DIN-rail (4-module) Modbus RTU
- Library ID
ime_nemo_d4_le_advanced- Access
- 187 read, 3 write
- Register areas
- holding
IME Nemo D4-Le (Basic)
Multifunction 3-phase network analyser DIN-rail (4-module) Modbus RTU
- Library ID
ime_nemo_d4_le_basic- Access
- 17 read
- Register areas
- holding
Inepro PRO380
3-phase energy meter (PRO380-Mod register map, datasheet uses hex addresses 0x4000-0x6048)
- Library ID
pro380- Access
- 39 read, 7 write
- Register areas
- holding
iSMA TouchPoint
iSMA TouchPoint TP-B / TP-C-B / TP-C-DISP-B panels (Modbus RTU, V1.3)
- Library ID
isma_touchpoint- Access
- 77 read, 54 write
- Register areas
- holding, input
iSMA-B-4I4O-H
iSMA MINI series I/O module - 4 Digital Inputs and 4 Digital Outputs
- Library ID
isma_4i4o- Access
- 34 read, 24 write
- Register areas
- holding, input
iSMA-B-4O-H
iSMA MINI series I/O module - 4 Digital Outputs (NC/NO 8A relay)
- Library ID
isma_4o- Access
- 19 read, 9 write
- Register areas
- holding, input
iSMA-B-4TO-H
iSMA MINI series I/O module - 4 Triac Outputs
- Library ID
isma_4to- Access
- 31 read, 21 write
- Register areas
- holding, input
iSMA-B-4U4A-H
iSMA MINI series I/O module - 4 Universal Inputs and 4 Analog Outputs (with relay capability)
- Library ID
isma_4u4a- Access
- 57 read, 30 write
- Register areas
- holding, input
iSMA-B-4U4O-H
iSMA MINI series I/O module - 4 Universal Inputs and 4 Analog Outputs
- Library ID
isma_4u4o- Access
- 75 read, 48 write
- Register areas
- holding, input
iSMA-B-8I
iSMA MINI series I/O module - 8 Digital Inputs
- Library ID
isma_8i- Access
- 26 read, 16 write
- Register areas
- holding, input
iSMA-B-8U
iSMA MINI series I/O module - 8 Universal Inputs
- Library ID
isma_8u- Access
- 58 read, 24 write
- Register areas
- holding, input
iSMA-B-MIX18
iSMA MIX series I/O module - 5 UI, 5 DI, 4 AO, 4 DO
- Library ID
isma_mix18- Access
- 66 read, 40 write
- Register areas
- holding, input
iSMA-B-MIX38
iSMA MIX series I/O module - 8 UI, 12 DI, 6 AO, 12 DO
- Library ID
isma_mix38- Access
- 94 read, 59 write
- Register areas
- holding, input
Janitza UMG 96RM (Advanced)
96x96 panel-mount power analyser with RS485 Modbus RTU
- Library ID
janitza_umg96rm_advanced- Access
- 134 read, 60 write
- Register areas
- holding
Janitza UMG 96RM (Basic)
96x96 panel-mount power analyser with RS485 Modbus RTU
- Library ID
janitza_umg96rm_basic- Access
- 19 read
- Register areas
- holding
Janitza UMG 96RM-E (Advanced)
96x96 panel-mount power analyser with RCM, RS485 Modbus RTU + Ethernet
- Library ID
janitza_umg96rm_e_advanced- Access
- 127 read, 63 write
- Register areas
- holding
Janitza UMG 96RM-E (Basic)
96x96 panel-mount power analyser with RCM, RS485 Modbus RTU + Ethernet
- Library ID
janitza_umg96rm_e_basic- Access
- 19 read
- Register areas
- holding
Kamstrup Multical (Advanced)
Heat/cooling/water meter Modbus RTU module for Multical 62/601/602/801
- Library ID
kamstrup_multical_advanced- Access
- 50 read
- Register areas
- holding
Kamstrup Multical (Basic)
Heat/cooling/water meter Modbus RTU module for Multical 62/601/602/801
- Library ID
kamstrup_multical_basic- Access
- 8 read
- Register areas
- holding
Kamstrup Multical 403/603 (Advanced)
Kamstrup heat/cooling meter Modbus RTU register map (default datagram)
- Library ID
kamstrup_403_603_advanced- Access
- 179 read
- Register areas
- holding
Kamstrup Multical 403/603 (Basic)
Kamstrup heat/cooling meter Modbus RTU register map (default datagram)
- Library ID
kamstrup_403_603_basic- Access
- 9 read
- Register areas
- holding
Kamstrup Multical 62/601/602/6L2/6M2/801 (Advanced)
Kamstrup heat-meter map - word-addressed only (byte-addressed range omitted)
- Library ID
kamstrup_multical_62_601_advanced- Access
- 65 read
- Register areas
- holding
Kamstrup Multical 62/601/602/6L2/6M2/801 (Basic)
Kamstrup heat-meter map - word-addressed only (byte-addressed range omitted)
- Library ID
kamstrup_multical_62_601_basic- Access
- 8 read
- Register areas
- holding
Lowara ecocirc XL / XLplus
Lowara ecocirc XL / XLplus wet-rotor circulator pump, Modbus RTU
- Library ID
lowara_ecocirc_xlplus- Access
- 69 read, 22 write
- Register areas
- holding
Lowara Q-Smart
Lowara Q-Smart Modbus pump control panel kit (2-pump booster / sewage / pressure / level)
- Library ID
lowara_q_smart- Access
- 90 read, 70 write
- Register areas
- holding
Lowara Smart Pump Range
Lowara Smart Pump Range (e-HME / e-SVE / VME / e-SVIE) Modbus RTU parameter list
- Library ID
lowara_smart_pump- Access
- 70 read, 41 write
- Register areas
- holding
OJ DRHX
OJ Electronics DRHX Modbus drive for rotary heat exchangers. Default Modbus ID 79, 38.4 kBd, 8N1
- Library ID
oj_drhx- Access
- 112 read, 55 write
- Register areas
- coil, discrete, holding, input
OJ Dual-PTH
OJ Electronics PTH-6201-2 / PTH-6202-2 / PTH-6501-2 dual pressure + dual temperature transmitter. 38.4 kBd 8N1, address range 180-195
- Library ID
oj_dual_pth- Access
- 32 read, 10 write
- Register areas
- coil, holding, input
OJ HTH-6200
OJ Electronics HTH-6202/6203/6204 duct humidity + temperature transmitter. Fixed addr 122/123/124, 38.4 kBaud 8N1
- Library ID
oj_hth_6200- Access
- 3 read
- Register areas
- input
OJ HTH-624x
OJ Electronics HTH-6242/6243/6244/6245 duct humidity + temperature transmitter. Fixed addr 122/123/124/125, 38.4 kBaud 8N1
- Library ID
oj_hth_624x- Access
- 3 read
- Register areas
- input
OJ TTH-6202
OJ Electronics TTH-6202 duct temperature transmitter. Fixed addr 170 (0xAA), 38.4 kBaud 8N1
- Library ID
oj_tth_6202- Access
- 3 read
- Register areas
- input
OJ VTH-6202/6242
OJ Electronics VTH-6202/6242 VOC air quality sensor. Modbus RS-485 38.4 kBd 8N2 no parity, fixed addr 110 (0x6E). Datasheet does not list registers — structure assumed by OJ family convention
- Library ID
oj_vth_6202_6242- Access
- 3 read
- Register areas
- input
Omron Yaskawa V1000
Yaskawa V1000 / Omron V1000 AC drive (MEMOBUS/Modbus RTU)
- Library ID
omron_v1000- Access
- 149 read, 26 write
- Register areas
- holding
Produal HDH
Room CO2 / temperature / humidity transmitter with Modbus RTU (RS-485) (Swedish doc)
- Library ID
produal_hdh- Access
- 58 read, 46 write
- Register areas
- coil, discrete, holding, input
Produal HLS 44-3P
3-pipe FCU room temperature controller with Modbus RTU (RS-485)
- Library ID
produal_hls44_3p- Access
- 95 read, 69 write
- Register areas
- coil, discrete, holding, input
Produal HLS 44-SE
Room temperature and VAV controller with Modbus RTU (RS-485)
- Library ID
produal_hls44_se- Access
- 118 read, 88 write
- Register areas
- coil, discrete, holding, input
Produal KLK 100
Duct humidity and temperature transmitter with Modbus RTU (RS-485)
- Library ID
produal_klk100- Access
- 33 read, 28 write
- Register areas
- coil, discrete, holding, input
Produal PEL / PEL-M
Duct differential pressure transmitter with Modbus RTU (RS-485)
- Library ID
produal_pel- Access
- 8 read, 4 write
- Register areas
- holding, input
Regin Corrigo Ventilation
Pre-programmed ventilation controller (3.6) - Modbus map covering coils, input registers, holding registers, and discrete inputs
- Library ID
corrigo- Access
- 175 read, 106 write
- Register areas
- coil, discrete, holding, input
Regin Regio RCX (Basic)
Regin Regio RCX room controller (T/RH/CO2/VOC) - key live values, setpoints and operating-mode settings
- Library ID
regin_regio_rcx_basic- Access
- 22 read, 9 write
- Register areas
- coil, holding, input
Schneider Altistart ATS480
Soft starter for asynchronous motors
- Library ID
schneider_ats480- Access
- 31 read, 14 write
- Register areas
- holding
Schneider ComPacT NS
ComPacT NS molded-case circuit breaker with MicroLogic A/E/P/H trip unit (Modbus standard dataset and MicroLogic registers)
- Library ID
schneider_ns- Access
- 159 read
- Register areas
- holding
Schneider ComPact NSX
ComPact NSX molded-case circuit breaker with MicroLogic A/E trip unit (Modbus standard dataset and MicroLogic registers)
- Library ID
schneider_nsx- Access
- 160 read
- Register areas
- holding
Schneider iEM3100 series (Advanced)
Single/three phase energy meter (iEM3100/3200/3300 series)
- Library ID
schneider_iem3100_advanced- Access
- 88 read, 20 write
- Register areas
- holding
Schneider iEM3100 series (Basic)
Single/three phase energy meter (iEM3100/3200/3300 series)
- Library ID
schneider_iem3100_basic- Access
- 17 read
- Register areas
- holding
Schneider MasterPact NT/NW
MasterPact NT and NW air circuit breakers with MicroLogic A/E/P/H trip unit (Modbus standard dataset and MicroLogic registers)
- Library ID
schneider_masterpact_nt_nw- Access
- 159 read
- Register areas
- holding
Schneider PowerLogic PM5500 (Advanced)
Power/energy meter, PM5560/PM5561/PM5563 (PM55xx/PM56xx series), standard PowerLogic FLOAT32 measurement registers
- Library ID
schneider_pm5500_advanced- Access
- 56 read
- Register areas
- holding
Schneider PowerLogic PM5500 (Basic)
Power/energy meter, PM5560/PM5561/PM5563 (PM55xx/PM56xx series), standard PowerLogic FLOAT32 measurement registers
- Library ID
schneider_pm5500_basic- Access
- 17 read
- Register areas
- holding
Schneider Vigirex RHU
Residual-current protection relay (VigiPacT RHU/RHUs), Modbus earth-leakage monitoring
- Library ID
schneider_vigirex- Access
- 12 read, 5 write
- Register areas
- holding
Siemens Climatix AHU
Climatix AHU application V3.3x Modbus reference addresses (addresses 1-based in datasheet, stored 0-based here)
- Library ID
climatix_ahu- Access
- 413 read, 188 write
- Register areas
- coil, discrete, holding, input
Siemens G110/G120/MM440 Drive
Modbus/TCP gateway register map for Siemens G110/G120/MM440 (MicroBridge ICP Panel-Tec)
- Library ID
siemens_g120p- Access
- 84 read, 31 write
- Register areas
- holding
Siemens QAE/QAM/QFM/QPM
Siemens duct/immersion T/RH/CO2/IAQ/VOC sensors Modbus RTU
- Library ID
siemens_qae_qam_qfm- Access
- 23 read, 11 write
- Register areas
- holding
Siemens RVD144
Siemens Synco 100 RVD144 district heating and DHW controller (RVD140-based OEM variant, plant type 4) - Modbus RTU RS-485 slave, FC 3/6/16, all registers signed 16-bit, temperatures 1/64 degC per bit. Defaults 9600 baud 8E1, bus off (address ---) until an address 1-247 is set on line 171
- Library ID
siemens_rvd144- Access
- 118 read, 54 write
- Register areas
- holding
Siemens SED2
Siemens SED2 VFD via SED2-MODBUS2 interface (scales are best-guess: many regs use raw x 0.01/0.1 vs P2000 nominal - verify with device)
- Library ID
siemens_sed2- Access
- 63 read, 23 write
- Register areas
- holding
Siemens SITRANS F MAG/MASS 6000
Siemens SITRANS F MAG 6000 / MASS 6000 flow meter Modbus RTU (FDK-085U0234 module)
- Library ID
siemens_sitrans- Access
- 63 read, 34 write
- Register areas
- holding
Siemens VersiCharge AC
EV charger Modbus RTU/TCP map (FW V2.120+)
- Library ID
siemens_versicharge- Access
- 50 read, 9 write
- Register areas
- holding
Socomec DIRIS A40/A41 (Advanced)
96x96 panel-mount multifunction power meter with RS485 JBUS/Modbus RTU
- Library ID
socomec_diris_a40_a41_advanced- Access
- 141 read, 31 write
- Register areas
- holding
Socomec DIRIS A40/A41 (Basic)
96x96 panel-mount multifunction power meter with RS485 JBUS/Modbus RTU
- Library ID
socomec_diris_a40_a41_basic- Access
- 17 read
- Register areas
- holding
Swegon CASA Smart
Residential AHU SEM/SEC (SCB 3.0+)
- Library ID
swegon_casa- Access
- 187 read, 93 write
- Register areas
- holding, input
Swegon GOLD RX/PX/CX/SD
Air handling unit GOLD generation E/F
- Library ID
swegon_gold- Access
- 50 read, 15 write
- Register areas
- coil, discrete, holding, input
Swegon SilverC RX
Rotary heat exchanger controls (Modbus RTU)
- Library ID
swegon_silvercrx- Access
- 66 read, 25 write
- Register areas
- coil, discrete, holding, input
Trox XDMB0
Trox XDMB0 dual-bus (BACnet MS/TP and Modbus RTU) controller for TVE/TVE-Q VAV terminal units — Modbus side of the register set
- Library ID
trox_xdmb0- Access
- 24 read, 16 write
- Register areas
- holding
Trox XM0
Trox XM0 compact controller for TVE/TVE-Q VAV terminal units, Modbus RTU register set
- Library ID
trox_xm0- Access
- 26 read, 17 write
- Register areas
- holding
Trox XM0-J6
Trox XM0-J6 compact controller for TVE/TVE-Q VAV terminal units with X-AIRCONTROL — Modbus register set identical to standard XM0
- Library ID
trox_xm0_j6- Access
- 24 read, 16 write
- Register areas
- holding
TTM NoXygen C625
TTM Energi NoXygen C625 vacuum degasser for hydronic heating systems. Modbus RTU 9600 8N1.
- Library ID
ttm_noxygen_c625- Access
- 47 read, 13 write
- Register areas
- holding, input
Unknown manufacturer
Roth Touchline SL
Roth Touchline SL wireless underfloor heating (Master L-12 + up to 3 extension controllers, 48 zones) - native Modbus RTU on the master's BMS/Modbus terminal (FW 1.0.11+), default address 1, 19200 8E1 - per-zone values are blocks of 48 registers (zone N = block start + N-1), heating flags packed 16 zones per register - room temp, setpoint and heating flag per zone, heat/cool mode and status, pumps, outside temp
- Library ID
roth_touchline_sl- Access
- 158 read, 53 write
- Register areas
- holding
Vacon 100 Flow
Vacon 100 Flow AC drive Modbus TCP/UDP and Modbus RTU fieldbus interface
- Library ID
vacon100_flow- Access
- 103 read, 27 write
- Register areas
- coil, discrete, holding, input
HAN2X Gen2
HAN/Modbus gateway
- Library ID
varibits-han2x- Access
- Not available
- Register areas
- 2, 3
VEGA VEGAPULS C 11/C 21/C 22/C 23
VEGA VEGAPULS C 11, C 21, C 22, C 23 compact radar level sensors. Shared Modbus RTU register set across antenna variants. Floats can be read at register banks 100+ (CDAB), 2002+ (ABCD), 2102+ (DCBA), 2202+ (BACD). This map uses the ABCD bank.
- Library ID
vegapuls_c11_c23- Access
- 25 read, 14 write
- Register areas
- holding, input
Wilo Para MAXO
Wilo Para MAXO Modbus RTU IF-Module (firmware 1.00-99.99)
- Library ID
wilo_para_maxo- Access
- 32 read, 12 write
- Register areas
- holding, input
Wilo Stratos IF-Module
Wilo IF-Module Modbus RTU for Stratos series (Stratos, GIGA, TOP-E, BL-E, IL-E, DL-E, MVIE, Helix VE/EXCEL)
- Library ID
wilo_stratos_if- Access
- 57 read, 11 write
- Register areas
- holding, input
Xylem Flygt Protocol Translator (MultiTrode)
Xylem Flygt Protocol Translator / MultiTrode MTT - Modbus gateway for MultiTrode monitrpr / MTxPC pump controllers
- Library ID
xylem_flygt_pt- Access
- 80 read, 10 write
- Register areas
- coil, discrete, holding, input
Xylem Hydrovar HVL
Xylem Hydrovar HVL (2.015 - 4.220) pump-mounted variable-speed controller, Modbus RTU
- Library ID
xylem_hydrovar_hvl- Access
- 126 read, 99 write
- Register areas
- holding
Xylem Hydrovar Legacy (HV 2.015-2.022)
Older Xylem/Lowara Hydrovar HV 2.015 / 2.022 pump-mounted controller, Modbus RTU
- Library ID
xylem_hydrovar_legacy- Access
- 110 read, 95 write
- Register areas
- holding
Xylem Hydrovar X EXM
Xylem Hydrovar X / X+ Series motor with integrated VSD (EXM), Modbus RTU
- Library ID
xylem_hydrovar_x_exm- Access
- 162 read, 116 write
- Register areas
- holding
No matching devices