No Modbus TCP communication with HAN2X
If you can open the HAN2X web interface, the device is connected to the IP network. Continue with the Modbus-specific checks:
- Use the current HAN2X IP address and the Modbus TCP port configured under Settings. The default port is 502.
- Confirm that the client uses the configured Modbus unit or slave address.
- Check whether the client expects zero-based register offsets or 4xxxx reference numbers.
- As a basic read test, request meter power from holding registers 40001–40002. The value spans two 16-bit registers and is represented as a 32-bit integer; confirm byte and word order in the current manual.
If the test fails, record the exact request, unit address, exception or timeout, and HAN2X firmware version.